Advanced dryer heat pumps
Innovative cycles for drying

Advanced dryer heat pumps | Ahuora Centre

Dryer inlet air at 100–220 °C, with heat recovered from warm water or air

Live design solves one cycle at a time here with CoolProp: recuperative RHP-A, B and C, the split-stream SLTHP, a transcritical–transcritical CO₂ cascade, an n-level cascade, or a heat pump with MVR steam (HP + MVR). Choose the refrigerants, the air and source-water temperatures, the approach and the design variables, or load an RHP-A or SLTHP design from the study. Static results are the REFPROP design study of RHP-A and the SLTHP.

Loading CoolProp…

Cycle

Refrigerant

Composition basis

Compressor and Expander

Efficiency model
Expansion

The low-stage swept volume sets the duties and flows; the COP does not depend on it.

Design

Compression
Internal heat exchanger

The gas-cooler pressure is solved (the lowest at which the gas-cooler pinch reaches the approach) and the gas-cooler outlet offset is optimised for COP: the gas-cooler outlet sits at air inlet + approach + offset, and an offset keeps stage 1 out of wet compression.

Load the study design

Operating point

Dryer air

Air inlet humidity

Heat source

Source air humidity

Minimum approaches

The evaporator pressure is the highest at which the evaporator and superheater stay 5 K below the source water (counterflow); the superheater outlet is 5 K below the water inlet.

Cases

Loading cases…

Cycle diagrams

One cycle at a time, coloured by component, with the bubble and dew lines of its fluid.

Temperature–entropy

Pressure–enthalpy

Heat exchange profiles

Temperature against heat transferred: the exchangers with the dryer air and the heat source. Dashed: the dryer air (grey) and the heat source (blue), named in the legend; shaded: the heat transfer between the streams. The exchangers on the dryer air are stacked in the order the air passes them, so the air reads as one continuous line.

Internal heat exchange

Recuperators, internal heat exchangers and cascade exchangers (and the HP + MVR steam generator): heat passed between the cycle's own streams. Solid: the hot side; dashed in the same colour: that exchanger's cold side, named in the legend; shaded: the heat transfer.

high-pressure sidelow-pressure sidedryer airsource waternumbers: refrigerant °C at each point; pressures in bar abs; duties in kW (heat ▲ to air, ▼ from water; electrical input at the compressors)

Method notes

RHP-A results come from main_RHPdesignA_caps.py: a fixed grid of RHX1 lift (0–125 K, within the 2/3-rule limit) and stage-2 power share (0.40–0.55), with the gas-cooler outlet offset optimised for each design. Its gas-cooler pressure follows from the design, so the limit simply removes designs above it.

SLTHP results come from main_SLTHP_compare.py with no pressure cap: RHX1 lift 30–140 K at a 0.50 power share, with the gas-cooler pressure and RHX1 flow share optimised inside each design. Each design keeps its pressure scan (36 points, 5–60 bar). Under a limit, the page uses the optimum where it fits and otherwise the best scan point below the limit, so the SLTHP under a limit is resolved to about 7 % in pressure.

Design choice: "Highest COP" takes the strict optimum. "Lowest pressure within 1 %" takes the lowest-pressure design whose COP is within 1 % of that optimum. The difference matters at a 30 K approach, where RHP-A at 150–170 °C has a second family of designs with no RHX1 lift at 45–68 bar that ties the recuperated designs at about 20 bar to within 0.04–1 % COP; the strict optimum then jumps between the two. The SLTHP has the same effect once (20/80, 170 °C, 20 K, 43 bar).

Headline pressures: maximum pressure and overall pressure ratio are the highest, and low-stage suction pressure the lowest, across the six air temperatures. For the SLTHP, designs taken from a pressure-scan point (the 1 % rule) use the suction pressure of that lift's optimum, marked ≈.

Live design: the same two cycle models (RecuperativeHeatPump Design A and SplitHeatPump.evaluate) in JavaScript over CoolProp 8 (HEOS mixtures), with the same compressor model (Pareto front isentropic efficiency, motor 0.93). Two things differ from the study. The source water has a finite flow from its inlet to its outlet temperature, and the evaporator pressure is the highest at which the evaporator and superheater stay 5 K below it; the study used an isothermal 40 °C source with the evaporator inlet held at 10 °C. And the RHP-A gas-cooler outlet offset is optimised continuously for COP (the study tried 0, 7, 10, 15, 20 and 30 K in turn until stage 1 was dry). Run on the study's own evaporator setting, the models reproduce the REFPROP COP to within about 0.02 % for the propane, butane and pentane blends, and to about 0.4 % for propane/cyclopentane (CoolProp's mixing parameters). The SLTHP's gas-cooler pressure and RHX1 flow share are inputs; an approach shortfall under 0.3 K is reported rather than failed.

Duties and power: refrigerant mass flow = stage-1 suction density × volumetric efficiency × low-stage swept volume. "Model" volumetric efficiency uses the pressure-ratio correlation in the cycle model (1 − 0.0824·(PR−1)^0.728); "Fixed" applies the chosen value to both cycles. For reference, a commercial screw compressor of this size is listed at 197 m³/h (50 Hz), and a commercial low-stage compressor at 145 m³/h (2950 rpm). High-stage swept volume needed = mass flow / (stage-2 suction density × stage-2 volumetric efficiency). Electrical input includes a motor efficiency of 0.93.

Refrigerant charge: a screening range, not a design or a filling quantity. The cycle fixes each exchanger's duty, driving force and refrigerant state; assumed overall coefficients and internal volumes per unit area then give its volume. The range runs from compact geometry with homogeneous two-phase density to bulky geometry with the Zivi void fraction; the central value uses typical geometry with Zivi. The system figure adds an allowance for oil, piping and receivers, based on small propane units (Dawoud et al., Energy Conversion and Management 372, 2027), so it is least certain at large capacities. Use it to compare designs at the same bound. For mixtures, the shift between charged and circulating composition is not modelled. Available for the RHP, flash tank / economiser and multi-pressure cycles; the economiser exchanger itself is not counted.

Data: results/dryer_compare_v26 (dashboard_data.json, cycles_data.json, state_5C_1bar.json); tables in results/dryer_compare_v26/summary.md.